Assessment Year | 1982 |
---|---|
Principal Product | CONTROLS FOR INDUSTRIES |
NAICS |
n/a
|
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
n/a
|
Annual Production | 300
pieces
|
Production Hrs. Annual | 4,225
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $138,216 | 3,596,131 |
kWh
|
$0.038 |
Natural Gas | $13,237 | 4,998 |
MMBtu
|
$2.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $79,774 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,156 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,333 | $19,254 |
$8,333
190,211
kWh
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $46 | $9 |
$46
1,172
kWh
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $647 | $997 |
$647
12,603
kWh
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,156 | $155 |
$8,156
220,399
kWh
|
|
05 | 2.7226: Use computer programs to optimize hvac performance | $57,720 | $28,000 |
$57,720
1,564,478
kWh
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,805 | $1,112 |
$1,805
47,479
kWh
|
|
07 | 2.7314: Reduce ventilation air | $487 | $235 |
$487
13,189
kWh
|
|
08 | 2.7422: Plant trees or shrubs near windows to shield from sunlight | $2,580 | $4,765 |
$2,580
69,754
kWh
|
|
TOTAL RECOMMENDED | $79,774 | $54,527 |
$79,774
2,119,285
kWh
|
||
TOTAL IMPLEMENTED | $8,156 | $155 |
$8,156
220,399
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs