| Assessment Year | 1999 |
|---|---|
| Principal Product | Polymer Insulators |
| NAICS |
n/a
|
| SIC | 3629: Electrical Industrial Apparatus, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 135 |
| Plant Area |
110,000
ft2
|
| Annual Production | 14,000,000
pieces
|
| Production Hrs. Annual | 4,076
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $77,819 | 3,652,403 |
kWh
|
$0.021 |
| Electricity Demand | $116,244 | 9,840 |
kW-mo/yr
|
$11.81 |
| Electricity Fees | $7,044 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $14,918 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,834 | $61,640 |
$4,823
225,381
kWh
|
$8,011
-
kW-mo/yr
|
|
| 02 | 2.4113: Install motor voltage controller on lightly loaded motors | $447 | $4,020 |
$383
17,878
kWh
|
$64
-
kW-mo/yr
|
|
| 03 | 2.2611: Moderate cooling tower outlet temperature | $82 | $20 |
$82
3,810
kWh
|
- | |
| 04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,555 | $2,000 |
$1,555
72,685
kWh
|
- | |
| TOTAL RECOMMENDED | $14,918 | $67,680 |
$6,843
319,754
kWh
|
$8,075
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs