| Assessment Year | 1998 |
|---|---|
| Principal Product | Polyethylene Stretch Film |
| NAICS |
n/a
|
| SIC | 3081: Unsupported Plastics Film and Sheet |
| Sales Range | $10 M to 50M |
| # of Employees | 44 |
| Plant Area |
75,000
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $77,608 | 4,801,290 |
kWh
|
$0.016 |
| Electricity Demand | $124,050 | 8,303 |
kW-mo/yr
|
$14.94 |
| Electricity Fees | $8,113 | - |
|
- |
| Natural Gas | $16,952 | 2,800 |
MMBtu
|
$6.05 |
| LPG | $5,196 | 292 |
MMBtu
|
$17.79 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $18,106 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2515: Use optimum thickness insulation | $7,666 | $21,040 | - | - |
$7,666
-
MMBtu
|
|
| 02 | 2.7135: Install occupancy sensors | $609 | $200 |
$609
37,515
kWh
|
- | - | |
| 03 | 2.4133: Use most efficient type of electric motors | $592 | $1,290 |
$202
12,603
kWh
|
$390
-
kW-mo/yr
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,239 | $16,477 |
$4,017
247,948
kWh
|
$5,222
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $18,106 | $39,007 |
$4,828
298,066
kWh
|
$5,612
-
kW-mo/yr
|
$7,666
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs