| Assessment Year | 1997 |
|---|---|
| Principal Product | Synthetic Fiber |
| NAICS |
n/a
|
| SIC | 2221: Broadwoven Fabric Mills, Manmade Fiber and Silk |
| Sales Range | $5 M to 10M |
| # of Employees | 150 |
| Plant Area |
260,074
ft2
|
| Annual Production | 11,000,000
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $400,694 | 24,991,208 |
kWh
|
$0.016 |
| Electricity Demand | $541,850 | 39,735 |
kW-mo/yr
|
$13.64 |
| Electricity Fees | $14,869 | - |
|
- |
| Natural Gas | $160,363 | 45,835 |
MMBtu
|
$3.50 |
| Fuel Oil #2 | $121,593 | 28,870 |
MMBtu
|
$4.21 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $125,793 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $81,151 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.2622: Replace existing chiller with high efficiency model | $32,105 | $53,256 |
$14,755
922,333
kWh
|
$17,350
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $19,107 | $1,495 | - | - |
$19,107
-
MMBtu
|
- | - | |
| 03 | 2.2414: Use waste heat from hot flue gases to preheat | $9,578 | $6,300 | - | - |
$9,578
-
MMBtu
|
- | - | |
| 04 | 2.4133: Use most efficient type of electric motors | $562 | $2,705 |
$365
22,860
kWh
|
$197
-
kW-mo/yr
|
- | - | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,299 | $9,865 |
$4,262
266,413
kWh
|
$5,037
-
kW-mo/yr
|
- | - | - | |
| 06 | 3.4116: Meter recycled water (to reduce sewer charges) | $10,500 | $4,095 | - | - | - |
$10,500
-
Tgal
|
- | |
| 07 | 3.6122: Install solid waste incinerator for heat | $44,642 | $16,696 | - | - |
$38,342
-
MMBtu
|
- |
$6,300
-
lb
|
|
| TOTAL RECOMMENDED | $125,793 | $94,412 |
$19,382
1,211,606
kWh
|
$22,584
-
kW-mo/yr
|
$67,027
-
MMBtu
|
$10,500
-
Tgal
|
$6,300
-
lb
|
||
| TOTAL IMPLEMENTED | $81,151 | $77,716 |
$19,382
1,211,606
kWh
|
$22,584
-
kW-mo/yr
|
$28,685
-
MMBtu
|
$10,500
-
Tgal
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs