| Assessment Year | 1996 |
|---|---|
| Principal Product | Unfinished Chemical Products |
| NAICS |
n/a
|
| SIC | 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 125 |
| Plant Area |
1,015,380
ft2
|
| Annual Production | 140,000,000
lb
|
| Production Hrs. Annual | 8,568
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $353,037 | 20,787,808 |
kWh
|
$0.017 |
| Electricity Demand | $415,311 | 63,102 |
kW-mo/yr
|
$6.58 |
| Electricity Fees | $36,441 | - |
|
- |
| LPG | $26,658 | 3,524 |
MMBtu
|
$7.56 |
| Fuel Oil #6 | $514,140 | 178,739 |
MMBtu
|
$2.88 |
| Other Energy | $573,233 | 553,356 |
MMBtu
|
$1.04 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $57,875 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $20,154 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Energy Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,687 | $18,685 |
$3,972
238,570
kWh
|
$2,715
-
kW-mo/yr
|
- | |
| 02 | 2.4133: Use most efficient type of electric motors | $4,599 | $6,838 |
$3,005
176,729
kWh
|
$1,594
-
kW-mo/yr
|
- | |
| 03 | 2.1133: Adjust burners for efficient operation | $8,868 | $5,760 | - | - |
$8,868
-
MMBtu
|
|
| 04 | 3.4115: Recover and reuse cooling water | $37,721 | $10,940 |
$24,633
1,449,297
kWh
|
$13,088
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $57,875 | $42,223 |
$31,610
1,864,596
kWh
|
$17,397
-
kW-mo/yr
|
$8,868
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $20,154 | $31,283 |
$6,977
415,299
kWh
|
$4,309
-
kW-mo/yr
|
$8,868
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs