Assessment Year | 1996 |
---|---|
Principal Product | Tea products |
NAICS |
n/a
|
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 364 |
Plant Area |
250,000
ft2
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $297,978 | 14,953,400 |
kWh
|
$0.020 |
Electricity Demand | $355,763 | 29,331 |
kW-mo/yr
|
$12.13 |
Electricity Fees | $332,023 | - |
|
- |
Natural Gas | $131,183 | 59,083 |
MMBtu
|
$2.22 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $39,649 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2414: Use waste heat from hot flue gases to preheat | $10,211 | $13,391 | - | - |
$10,211
-
MMBtu
|
- | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,112 | $1,077 |
$493
24,912
kWh
|
$619
-
kW-mo/yr
|
- | - | |
03 | 2.4133: Use most efficient type of electric motors | $4,515 | $9,800 |
$2,914
65,944
kWh
|
$1,601
-
kW-mo/yr
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,780 | $3,754 |
$5,843
293,669
kWh
|
$4,937
-
kW-mo/yr
|
- | - | |
05 | 2.4323: Use optimum size and capacity equipment | $5,538 | $1,332 |
$3,015
151,524
kWh
|
$2,523
-
kW-mo/yr
|
- | - | |
06 | 3.4116: Meter recycled water (to reduce sewer charges) | $7,493 | $1,072 | - | - | - |
$7,493
-
Tgal
|
|
TOTAL RECOMMENDED | $39,649 | $30,426 |
$12,265
536,049
kWh
|
$9,680
-
kW-mo/yr
|
$10,211
-
MMBtu
|
$7,493
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs