Assessment Year | 2000 |
---|---|
Principal Product | Rolled Steel Bars |
NAICS |
n/a
|
SIC | 3556: Food Products Machinery |
Sales Range | $50 M to 100M |
# of Employees | 85 |
Plant Area |
88,200
ft2
|
Annual Production | 2,500,000
lb
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $145,829 | 3,536,049 |
kWh
|
$0.041 |
Electricity Demand | $120,327 | 12,500 |
kW-mo/yr
|
$9.63 |
Electricity Fees | $3,510 | - |
|
- |
Natural Gas | $153,978 | 37,467 |
MMBtu
|
$4.11 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,287 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,778 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | LPG Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $334 | $727 |
$261
6,448
kWh
|
$83
-
kW-mo/yr
|
$(-10.0) | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,444 | $300 |
$1,029
24,912
kWh
|
$462
-
kW-mo/yr
|
$(-47.0) | - | - | - | |
03 | 2.7231: Use radiant heater for spot heating | $3,476 | $1,368 |
$3,484
84,408
kWh
|
$2,310
-
kW-mo/yr
|
$(-180.0) | - |
$(-2,138.0)
-
MMBtu
|
- | |
04 | 4.454: Modify startup/shutdown times | $13,033 | - |
$3,315
82,943
kWh
|
- | - |
$7,384
-
MMBtu
|
- | $2,334 | |
TOTAL RECOMMENDED | $18,287 | $2,395 |
$8,089
198,711
kWh
|
$2,855
-
kW-mo/yr
|
$(-237.0) |
$7,384
-
MMBtu
|
$(-2,138.0)
-
MMBtu
|
$2,334 | ||
TOTAL IMPLEMENTED | $1,778 | $1,027 |
$1,290
31,360
kWh
|
$545
-
kW-mo/yr
|
$(-57.0) | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs