| Assessment Year | 1999 |
|---|---|
| Principal Product | Sporting & Athletic Goods |
| NAICS |
n/a
|
| SIC | 3949: Sporting and Athletic Goods, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 50 |
| Plant Area |
60,000
ft2
|
| Annual Production | 8,000,000
pieces
|
| Production Hrs. Annual | 2,210
hrs
|
| Location (State) | Nevada |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $16,836 | 403,283 |
kWh
|
$0.042 |
| Electricity Demand | $13,558 | 1,461 |
kW-mo/yr
|
$9.28 |
| Electricity Fees | $1,239 | - |
|
- |
| Natural Gas | $11,391 | 2,175 |
MMBtu
|
$5.24 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $8,504 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,246 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $258 | $562 |
$194
4,689
kWh
|
$59
-
kW-mo/yr
|
$5 | - | - | |
| 02 | 2.7243: Improve air circulation with destratification fans / other methods | $4,845 | $2,532 |
$(-115.0)
(-2,638)
kWh
|
$(-85.0)
-
kW-mo/yr
|
$(-4.0) |
$5,049
-
MMBtu
|
- | |
| 03 | 3.6192: Use a less expensive method of waste removal | $3,401 | - | - | - | - | - |
$3,401
-
lb
|
|
| TOTAL RECOMMENDED | $8,504 | $3,094 |
$79
2,051
kWh
|
$(-26.0)
-
kW-mo/yr
|
$1 |
$5,049
-
MMBtu
|
$3,401
-
lb
|
||
| TOTAL IMPLEMENTED | $8,246 | $2,532 |
$(-115.0)
(-2,638)
kWh
|
$(-85.0)
-
kW-mo/yr
|
$(-4.0) |
$5,049
-
MMBtu
|
$3,401
-
lb
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs