Assessment Year | 1999 |
---|---|
Principal Product | Bottled Soft Drinks |
NAICS |
n/a
|
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
81,200
ft2
|
Annual Production | 1,800,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $34,214 | 813,306 |
kWh
|
$0.042 |
Electricity Demand | $32,560 | 3,439 |
kW-mo/yr
|
$9.47 |
Electricity Fees | $3,177 | - |
|
- |
Natural Gas | $21,417 | 4,120 |
MMBtu
|
$5.20 |
Fuel Oil #2 | $6,832 | 1,019 |
MMBtu
|
$6.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $13,349 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,305 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Fuel Oil #2 Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $8,107 | $12,275 |
$9,166
106,096
kWh
|
- | - | - |
$(-1,059.0)
-
MMBtu
|
|
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $202 | $64 |
$137
3,224
kWh
|
$61
-
kW-mo/yr
|
$4 | - | - | |
03 | 2.7231: Use radiant heater for spot heating | $1,842 | $3,350 | - | - | - |
$(-3,282.0)
-
MMBtu
|
$5,124
-
MMBtu
|
|
04 | 2.8114: Change rate schedules or other changes in utility service | $3,198 | - | - | - | $3,198 | - | - | |
TOTAL RECOMMENDED | $13,349 | $15,689 |
$9,303
109,320
kWh
|
$61
-
kW-mo/yr
|
$3,202 |
$(-3,282.0)
-
MMBtu
|
$4,065
-
MMBtu
|
||
TOTAL IMPLEMENTED | $11,305 | $12,275 |
$9,166
106,096
kWh
|
- | $3,198 | - |
$(-1,059.0)
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs