Assessment Year | 1998 |
---|---|
Principal Product | Vinyl Sheeting |
NAICS |
n/a
|
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
66,000
ft2
|
Annual Production | 18,990,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $272,289 | 6,609,613 |
kWh
|
$0.041 |
Electricity Demand | $120,130 | 12,524 |
kW-mo/yr
|
$9.59 |
Electricity Fees | $2,384 | - |
|
- |
Natural Gas | $198,394 | 34,737 |
MMBtu
|
$5.71 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $308,678 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $299,524 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.1213: Direct warmest air to combustion intake | $2,386 | $333 | - | - | - |
$2,386
-
MMBtu
|
- | - | - | |
02 | 2.2511: Insulate bare equipment | $845 | $546 | - | - | - |
$845
-
MMBtu
|
- | - | - | |
03 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $278,123 | $520,000 | - | - | - | - | $278,123 | - | - | |
04 | 2.7124: Make a practice of turning off lights when not needed | $390 | - |
$332
8,206
kWh
|
$64
-
kW-mo/yr
|
$(-6.0) | - | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,185 | $10,360 |
$2,868
65,064
kWh
|
$356
-
kW-mo/yr
|
$(-39.0) | - | - | - | - | |
06 | 2.7145: Install skylights | $643 | $2,443 |
$395
9,672
kWh
|
$235
-
kW-mo/yr
|
$13 | - | - | - | - | |
07 | 2.8113: Purchase gas directly from a contract gas supplier | $21,011 | - | - | - | - | - | - | - | $21,011 | |
08 | 2.9112: Use solar heat to heat water | $2,095 | - | - | - | - |
$10,475
-
MMBtu
|
- | $(-8,380.0) | - | |
TOTAL RECOMMENDED | $308,678 | $533,682 |
$3,595
82,942
kWh
|
$655
-
kW-mo/yr
|
$(-32.0) |
$13,706
-
MMBtu
|
$278,123 | $(-8,380.0) | $21,011 | ||
TOTAL IMPLEMENTED | $299,524 | $520,000 |
$332
8,206
kWh
|
$64
-
kW-mo/yr
|
$(-6.0) | - | $278,123 | - | $21,011 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs