Assessment Year | 1996 |
---|---|
Principal Product | Rotary Cutting Tools |
NAICS |
n/a
|
SIC | 3541: Machine Tools, Metal Cutting Types |
Sales Range | $5 M to 10M |
# of Employees | 70 |
Plant Area |
42,500
ft2
|
Annual Production | 325,000
lb
|
Production Hrs. Annual | 5,460
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $91,659 | 1,044,256 |
kWh
|
$0.088 |
Electricity Demand | $13,918 | 3,005 |
kW-mo/yr
|
$4.63 |
Electricity Fees | $1,255 | - |
|
- |
Natural Gas | $993 | 149 |
MMBtu
|
$6.66 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,994 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,594 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $6,386 | $20 |
$5,829
66,530
kWh
|
$557
-
kW-mo/yr
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $743 | $200 |
$743
8,499
kWh
|
- | - | - | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $413 | - |
$374
4,396
kWh
|
$39
-
kW-mo/yr
|
- | - | - | |
04 | 2.7135: Install occupancy sensors | $968 | $282 |
$868
9,965
kWh
|
$100
-
kW-mo/yr
|
- | - | - | |
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,846 | $920 | - | - | - | - | $1,846 | |
06 | 2.4323: Use optimum size and capacity equipment | $3,238 | $180 | - | - | $3,238 | - | - | |
07 | 3.7393: Implement a machine and coolant sump cleaning program to minimize coolant contamination | $5,400 | $10,000 | - | - | - |
$5,400
-
gal
|
- | |
TOTAL RECOMMENDED | $18,994 | $11,602 |
$7,814
89,390
kWh
|
$696
-
kW-mo/yr
|
$3,238 |
$5,400
-
gal
|
$1,846 | ||
TOTAL IMPLEMENTED | $13,594 | $1,602 |
$7,814
89,390
kWh
|
$696
-
kW-mo/yr
|
$3,238 | - | $1,846 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs