| Assessment Year | 1998 |
|---|---|
| Principal Product | electronic control boards |
| NAICS |
n/a
|
| SIC | 3679: Electronic Components, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 750 |
| Plant Area |
144,000
ft2
|
| Annual Production | 4,200,000
pieces
|
| Production Hrs. Annual | 7,200
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $299,428 | 7,946,952 |
kWh
|
$0.038 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $14,284 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|
| 01 | 3.4151: Minimize water usage | $5,055 | $4,900 |
$1,527
75,029
kWh
|
$3,528
-
Tgal
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,614 | $36,601 |
$4,614
99,355
kWh
|
- | |
| 03 | 2.7221: Lower temperature during the winter season and vice-versa | $1,546 | $10,000 |
$1,546
41,032
kWh
|
- | |
| 04 | 2.7122: Disconnect ballasts | $1,286 | $1,320 |
$1,286
64,185
kWh
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $772 | $450 |
$772
38,687
kWh
|
- | |
| 06 | 2.7124: Make a practice of turning off lights when not needed | $419 | $50 |
$419
20,809
kWh
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $327 | $750 |
$327
586
kWh
|
- | |
| 08 | 2.6218: Turn off equipment when not in use | $265 | $338 |
$265
7,034
kWh
|
- | |
| TOTAL RECOMMENDED | $14,284 | $54,409 |
$10,756
346,717
kWh
|
$3,528
-
Tgal
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs