| Assessment Year | 1992 |
|---|---|
| Principal Product | PANELS FOR AUTO BODIES |
| NAICS |
n/a
|
| SIC | 3469: Metal Stampings, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 280 |
| Plant Area |
n/a
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 4,000
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $432,499 | 7,912,368 |
kWh
|
$0.055 |
| Natural Gas | $396,401 | 274,920 |
MMBtu
|
$1.44 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $61,323 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $43,266 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 3.4115: Recover and reuse cooling water | $24,397 | $25,000 |
$(-1,438.0)
(-26,377)
kWh
|
- | $25,835 | |
| 02 | 2.4133: Use most efficient type of electric motors | $2,600 | $16,570 |
$2,600
47,479
kWh
|
- | - | |
| 03 | 2.8114: Change rate schedules or other changes in utility service | $14,208 | $2,000 |
$14,208
-
kWh
|
- | - | |
| 04 | 2.8121: Apply for tax-free status for energy purchases | $1,628 | $200 |
$1,628
-
kWh
|
- | - | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,757 | $500 |
$10,757
196,952
kWh
|
- | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,338 | $5,000 |
$2,018
36,928
kWh
|
- | $(-680.0) | |
| 07 | 2.7111: Reduce illumination to minimum necessary levels | $3,564 | $2,000 |
$3,564
65,358
kWh
|
- | - | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $610 | $638 |
$610
11,137
kWh
|
- | - | |
| 09 | 2.7494: Install storm windows and doors | $1,647 | $3,713 | - |
$1,647
-
MMBtu
|
- | |
| 10 | 2.7494: Install storm windows and doors | $574 | $2,010 | - |
$574
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $61,323 | $57,631 |
$33,947
331,477
kWh
|
$2,221
-
MMBtu
|
$25,155 | ||
| TOTAL IMPLEMENTED | $43,266 | $49,708 |
$18,111
331,477
kWh
|
- | $25,155 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs