Assessment Year | 2018 |
---|---|
Principal Product | Hoses |
NAICS | 326220: Rubber and Plastics Hoses and Belting Manufacturing |
SIC | 3052: Rubber and Plastics Hose and Belting |
Sales Range | $10 M to 50M |
# of Employees | 160 |
Plant Area |
173,000
ft2
|
Annual Production | 4,000,000
units
|
Production Hrs. Annual | 6,600
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $212,975 | 3,338,420 |
kWh
|
$0.064 |
Electricity Demand | $53,478 | 12,322 |
kW-mo/yr
|
$4.34 |
Natural Gas | $206,912 | 45,118 |
MMBtu
|
$4.59 |
TOTAL YEARLY COSTS | $473,365 | |||
RECOMMENDED SAVINGS* | $52,963 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,870 | $54,127 |
$20,061
314,442
kWh
|
$2,809
-
kW-mo/yr
|
- | - | - | |
02 | 2.7135: Install occupancy sensors | $134 | $150 |
$134
2,100
kWh
|
- | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,222 | $390 |
$5,865
91,931
kWh
|
$747
-
kW-mo/yr
|
- | $(-300.0) | $(-90.0) | |
04 | 2.2136: Install / repair insulation on steam lines | $6,697 | $5,350 | - | - |
$6,697
-
MMBtu
|
- | - | |
05 | 2.2121: Increase amount of condensate returned | $943 | $1,000 | - | - |
$943
-
MMBtu
|
- | - | |
06 | 2.8114: Change rate schedules or other changes in utility service | $16,097 | $500 |
$16,097
-
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $52,963 | $61,517 |
$42,157
408,473
kWh
|
$3,556
-
kW-mo/yr
|
$7,640
-
MMBtu
|
$(-300.0) | $(-90.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs