Assessment Year | 2015 |
---|---|
Principal Product | Polyacrylate polymers |
NAICS | 325199: All Other Basic Organic Chemical Manufacturing |
SIC | 2899: Chemicals and Chemical Preparations, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 45 |
Plant Area |
65,000
ft2
|
Annual Production | 90,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $170,197 | 4,245,443 |
kWh
|
$0.040 |
Electricity Demand | $91,494 | 8,119 |
kW-mo/yr
|
$11.27 |
Electricity Fees | $984 | - |
|
- |
Natural Gas | $146,524 | 21,423 |
MMBtu
|
$6.84 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $28,958 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,706 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,747 | $10,826 |
$3,951
98,778
kWh
|
$1,674
-
kW-mo/yr
|
- | - | $122 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $524 | $3,462 |
$303
7,569
kWh
|
$128
-
kW-mo/yr
|
- | - | $93 | |
03 | 2.7135: Install occupancy sensors | $1,734 | $1,041 |
$1,734
43,362
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,614 | $7,461 |
$1,073
26,832
kWh
|
$910
-
kW-mo/yr
|
- | - | $(-369.0) | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,200 | $850 |
$1,426
36,653
kWh
|
$604
-
kW-mo/yr
|
- | $(-800.0) | $(-30.0) | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,823 | $4,175 |
$1,983
49,582
kWh
|
$840
-
kW-mo/yr
|
- | - | - | |
07 | 2.2123: Insulate feedwater tank | $1,506 | $1,204 | - | - |
$1,506
-
MMBtu
|
- | - | |
08 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $8,635 | $20,900 |
$11,563
289,080
kWh
|
$5,280
-
kW-mo/yr
|
$(-8,208.0)
-
MMBtu
|
- | - | |
09 | 2.2437: Recover waste heat from equipment | $5,175 | $20,000 |
$3,854
96,360
kWh
|
$1,321
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $28,958 | $69,919 |
$25,887
648,216
kWh
|
$10,757
-
kW-mo/yr
|
$(-6,702.0)
-
MMBtu
|
$(-800.0) | $(-184.0) | ||
TOTAL IMPLEMENTED | $2,706 | $2,054 |
$1,426
36,653
kWh
|
$604
-
kW-mo/yr
|
$1,506
-
MMBtu
|
$(-800.0) | $(-30.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs