Assessment Year | 2014 |
---|---|
Principal Product | Motors |
NAICS | 335312: Motor and Generator Manufacturing |
SIC | 3621: Motors and Generators |
Sales Range | $100 M to 500M |
# of Employees | 462 |
Plant Area |
259,000
ft2
|
Annual Production | 1,280
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $560,939 | 13,864,800 |
kWh
|
$0.040 |
Electricity Demand | $288,076 | 25,721 |
kW-mo/yr
|
$11.20 |
Electricity Fees | $703 | - |
|
- |
Natural Gas | $385,353 | 51,988 |
MMBtu
|
$7.41 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,476 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,362 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,097 | $100 |
$4,759
117,495
kWh
|
$1,878
-
kW-mo/yr
|
$(-300.0) | $(-240.0) | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,526 | $100 |
$3,245
80,113
kWh
|
$1,281
-
kW-mo/yr
|
- | - | |
03 | 2.4239: Eliminate or reduce compressed air usage | $1,799 | $150 |
$495
12,219
kWh
|
$1,304
-
kW-mo/yr
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,209 | $1,935 |
$2,300
56,800
kWh
|
$909
-
kW-mo/yr
|
- | - | |
05 | 2.7135: Install occupancy sensors | $917 | $650 |
$917
22,638
kWh
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $612 | $754 |
$404
9,979
kWh
|
$160
-
kW-mo/yr
|
- | $48 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $726 | $224 |
$232
5,739
kWh
|
$92
-
kW-mo/yr
|
- | $402 | |
08 | 2.7111: Reduce illumination to minimum necessary levels | $471 | $275 |
$306
7,557
kWh
|
$122
-
kW-mo/yr
|
- | $43 | |
09 | 2.3132: Recharge batteries on during off-peak demand periods | $1,119 | $100 |
$245
-
kWh
|
$874
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $19,476 | $4,288 |
$12,903
312,540
kWh
|
$6,620
-
kW-mo/yr
|
$(-300.0) | $253 | ||
TOTAL IMPLEMENTED | $17,362 | $3,139 |
$11,448
276,606
kWh
|
$6,406
-
kW-mo/yr
|
$(-300.0) | $(-192.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs