Assessment Year | 2014 |
---|---|
Principal Product | Injection molded plastic parts |
NAICS | 326121: Unlaminated Plastics Profile Shape Manufacturing |
SIC | 3082: Unsupported Plastics Profile Shapes |
Sales Range | $5 M to 10M |
# of Employees | 40 |
Plant Area |
44,341
ft2
|
Annual Production | 157,000,000
pieces
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $115,480 | 2,740,035 |
kWh
|
$0.042 |
Electricity Demand | $59,318 | 5,453 |
kW-mo/yr
|
$10.88 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,944 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,104 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,076 | $24,656 |
$8,438
200,421
kWh
|
$3,638
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,207 | $1,497 |
$579
13,754
kWh
|
$628
-
kW-mo/yr
|
- | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $218 | $75 |
$145
3,456
kWh
|
$63
-
kW-mo/yr
|
- | $10 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $272 | $80 |
$90
2,138
kWh
|
$32
-
kW-mo/yr
|
- | $150 | |
05 | 2.7135: Install occupancy sensors | $587 | $1,594 |
$587
13,934
kWh
|
- | - | - | |
06 | 2.2612: Use cooling tower water instead of refrigeration | $1,840 | $8,000 |
$1,430
33,961
kWh
|
$410
-
kW-mo/yr
|
- | - | |
07 | 2.7241: Install outside air damper / economizer on hvac unit | $2,479 | $5,500 |
$2,479
58,881
kWh
|
- | - | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $798 | $50 |
$558
13,248
kWh
|
$240
-
kW-mo/yr
|
- | - | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $467 | $50 |
$452
10,742
kWh
|
$195
-
kW-mo/yr
|
$(-100.0) | $(-80.0) | |
TOTAL RECOMMENDED | $19,944 | $41,502 |
$14,758
350,535
kWh
|
$5,206
-
kW-mo/yr
|
$(-100.0) | $80 | ||
TOTAL IMPLEMENTED | $18,104 | $33,502 |
$13,328
316,574
kWh
|
$4,796
-
kW-mo/yr
|
$(-100.0) | $80 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs