Assessment Year | 2013 |
---|---|
Principal Product | Plastic packaging |
NAICS | 326112: Plastics Packaging Film and Sheet (including Laminated) Manufacturing |
SIC | 2671: Packaging Paper and Plastics Film, Coated and Laminated |
Sales Range | $100 M to 500M |
# of Employees | 252 |
Plant Area |
282,000
ft2
|
Annual Production | 160,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,928,423 | 58,674,000 |
kWh
|
$0.033 |
Electricity Demand | $1,745,891 | 94,577 |
kW-mo/yr
|
$18.46 |
Natural Gas | $312,093 | 43,623 |
MMBtu
|
$7.15 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $267,315 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,256 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,366 | $33,811 |
$6,506
184,262
kWh
|
$4,860
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $76,174 | $132,415 |
$44,473
1,259,496
kWh
|
$33,215
-
kW-mo/yr
|
- | - | $(-1,514.0) | |
03 | 2.7135: Install occupancy sensors | $5,539 | $2,682 |
$5,539
156,878
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,981 | $2,248 |
$477
13,520
kWh
|
$343
-
kW-mo/yr
|
- | - | $1,161 | |
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $139,540 | $300,000 |
$169,064
4,788,000
kWh
|
$126,267
-
kW-mo/yr
|
$(-155,791.0)
-
MMBtu
|
- | - | |
06 | 2.2437: Recover waste heat from equipment | $11,303 | $4,000 |
$(-99.0)
(-2,800)
kWh
|
$(-74.0)
-
kW-mo/yr
|
$11,476
-
MMBtu
|
- | - | |
07 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $14,522 | $24,104 |
$(-204.0)
(-5,789)
kWh
|
$(-139.0)
-
kW-mo/yr
|
$14,865
-
MMBtu
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,890 | $100 |
$4,425
125,328
kWh
|
$3,305
-
kW-mo/yr
|
- | $(-600.0) | $(-240.0) | |
TOTAL RECOMMENDED | $267,315 | $499,360 |
$230,181
6,518,895
kWh
|
$167,777
-
kW-mo/yr
|
$(-129,450.0)
-
MMBtu
|
$(-600.0) | $(-593.0) | ||
TOTAL IMPLEMENTED | $18,256 | $33,911 |
$10,931
309,590
kWh
|
$8,165
-
kW-mo/yr
|
- | $(-600.0) | $(-240.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs