| Assessment Year | 2012 |
|---|---|
| Principal Product | Museum |
| NAICS | 712110: Museums |
| SIC | 8412: Museums and Art Galleries |
| Sales Range | less than $500 k |
| # of Employees | 25 |
| Plant Area |
12,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 4,400
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $65,074 | 1,255,200 |
kWh
|
$0.052 |
| Electricity Demand | $23,506 | 2,816 |
kW-mo/yr
|
$8.35 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $51,838 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $7,353 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings | Primary Product Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,289 | $5,115 |
$1,128
21,727
kWh
|
$495
-
kW-mo/yr
|
$1,666 | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,774 | $900 |
$876
16,878
kWh
|
$471
-
kW-mo/yr
|
$427 | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,836 | $175 |
$1,276
24,592
kWh
|
$560
-
kW-mo/yr
|
- | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $454 | $225 |
$158
3,043
kWh
|
$35
-
kW-mo/yr
|
$261 | - | |
| 05 | 2.7135: Install occupancy sensors | $134 | $529 |
$134
2,587
kWh
|
- | - | - | |
| 06 | 2.7232: Replace existing hvac unit with high efficiency model | $3,318 | $15,000 |
$1,691
35,602
kWh
|
$1,627
-
kW-mo/yr
|
- | - | |
| 07 | 4.424: Improve space comfort conditioning | $41,033 | $60,000 |
$(-3,114.0)
(-60,006)
kWh
|
$(-853.0)
-
kW-mo/yr
|
- | $45,000 | |
| TOTAL RECOMMENDED | $51,838 | $81,944 |
$2,149
44,423
kWh
|
$2,335
-
kW-mo/yr
|
$2,354 | $45,000 | ||
| TOTAL IMPLEMENTED | $7,353 | $6,415 |
$3,438
66,240
kWh
|
$1,561
-
kW-mo/yr
|
$2,354 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings | Primary Product Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs