Assessment Year 2011
Principal Product Electrical wiring devices
NAICS 335931: Current-Carrying Wiring Device Manufacturing
SIC 3643: Current-Carrying Wiring Devices
Sales Range $50
M
to 100
M
# of Employees 319
Plant Area 240,000
ft2
Annual Production 147,000,000
pieces
Production Hrs. Annual 6,000
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,079,930 24,218,579
kWh
Electricity Demand $488,509 52,462
kW-mo/yr
Electricity Fees $3,189 -
Natural Gas $56,695 7,393
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $61,739 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $16,590

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings Water Consumption Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $9,839 - $8,993
164,640
kWh
$846
-
kW-mo/yr
- - - -
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,052 $100 $5,119
93,720
kWh
$613
-
kW-mo/yr
- $(-1,200.0) $(-480.0) -
03 2.4239: Eliminate or reduce compressed air usage $1,314 $150 $1,161
21,250
kWh
$153
-
kW-mo/yr
- - - -
04 2.2614: Use cooling tower or economizer to replace chiller cooling $11,250 $22,950 $11,395
208,620
kWh
$1,502
-
kW-mo/yr
- - - $(-1,647.0)
-
Tgal
05 2.1224: Replace boiler $3,539 $11,800 - - $3,539
-
MMBtu
- - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $1,385 $4,833 $1,076
19,695
kWh
$309
-
kW-mo/yr
- - - -
07 2.2614: Use cooling tower or economizer to replace chiller cooling $30,360 $161,900 $35,791
655,268
kWh
- - - - $(-5,431.0)
-
Tgal
TOTAL RECOMMENDED $61,739 $201,733 $63,535
1,163,193
kWh
$3,423
-
kW-mo/yr
$3,539
-
MMBtu
$(-1,200.0) $(-480.0) $(-7,078.0)
-
Tgal
TOTAL IMPLEMENTED $16,590 $5,083 $16,349
299,305
kWh
$1,921
-
kW-mo/yr
- $(-1,200.0) $(-480.0) -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Ancillary Material Cost Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs