Assessment Year | 2010 |
---|---|
Principal Product | Power tools |
NAICS | 333991: Power-Driven Handtool Manufacturing |
SIC | 3546: Power-Driven Handtools |
Sales Range | greater than $500 M |
# of Employees | 2,000 |
Plant Area |
500,000
ft2
|
Annual Production | 3,240,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,980,028 | 45,390,896 |
kWh
|
$0.044 |
Electricity Demand | $1,148,860 | 81,329 |
kW-mo/yr
|
$14.13 |
Electricity Fees | $8,435 | - |
|
- |
Natural Gas | $363,822 | 35,115 |
MMBtu
|
$10.36 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $215,286 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $135,418 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7241: Install outside air damper / economizer on hvac unit | $35,525 | $20,000 |
$35,367
810,800
kWh
|
$158
-
kW-mo/yr
|
- | - | - | |
02 | 2.7245: Use direct air supply to exhaust hoods | $68,552 | $57,900 |
$32,084
735,525
kWh
|
$24,114
-
kW-mo/yr
|
$12,354
-
MMBtu
|
- | - | |
03 | 2.7229: Air condition only space necessary | $9,565 | $18,450 |
$6,976
159,922
kWh
|
$2,589
-
kW-mo/yr
|
- | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,697 | $200 |
$7,782
178,404
kWh
|
$2,915
-
kW-mo/yr
|
- | $(-4,800.0) | $(-1,200.0) | |
05 | 2.2437: Recover waste heat from equipment | $1,751 | $14,000 | - | - |
$1,751
-
MMBtu
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,554 | $1,205 |
$825
18,921
kWh
|
$729
-
kW-mo/yr
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $93,642 | $225,498 |
$67,206
1,540,726
kWh
|
$25,138
-
kW-mo/yr
|
- | $(-16,184.0) | $17,482 | |
TOTAL RECOMMENDED | $215,286 | $337,253 |
$150,240
3,444,298
kWh
|
$55,643
-
kW-mo/yr
|
$14,105
-
MMBtu
|
$(-20,984.0) | $16,282 | ||
TOTAL IMPLEMENTED | $135,418 | $246,903 |
$111,180
2,548,851
kWh
|
$28,940
-
kW-mo/yr
|
- | $(-20,984.0) | $16,282 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs