| Assessment Year | 2009 |
|---|---|
| Principal Product | Conveyor rollers |
| NAICS | 333922: Conveyor and Conveying Equipment Manufacturing |
| SIC | 3535: Conveyors and Conveying Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 80 |
| Plant Area |
228,297
ft2
|
| Annual Production | 1,000,000
pieces
|
| Production Hrs. Annual | 4,250
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $139,471 | 2,811,000 |
kWh
|
$0.050 |
| Electricity Demand | $64,608 | 7,321 |
kW-mo/yr
|
$8.83 |
| Electricity Fees | $3,040 | - |
|
- |
| LPG | $7,091 | 415 |
MMBtu
|
$17.09 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $150,997 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7232: Replace existing hvac unit with high efficiency model | $76,612 | $275,318 |
$23,560
427,281
kWh
|
$13,052
-
kW-mo/yr
|
- | - | $40,000 | |
| 02 | 4.512: Condense operation into one building | $31,185 | $13,100 |
$20,537
362,468
kWh
|
$8,544
-
kW-mo/yr
|
- |
$2,104
-
MMBtu
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $37,090 | $83,137 |
$26,319
475,983
kWh
|
$11,222
-
kW-mo/yr
|
- | - | $(-451.0) | |
| 04 | 2.7135: Install occupancy sensors | $600 | $558 |
$600
10,585
kWh
|
- | - | - | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $313 | $132 |
$102
1,800
kWh
|
$80
-
kW-mo/yr
|
- | - | $131 | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,507 | - |
$1,064
18,785
kWh
|
$443
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.2437: Recover waste heat from equipment | $3,690 | $5,306 | - | - |
$3,690
-
MMBtu
|
- | - | |
| TOTAL RECOMMENDED | $150,997 | $377,551 |
$72,182
1,296,902
kWh
|
$33,341
-
kW-mo/yr
|
$3,690
-
MMBtu
|
$2,104
-
MMBtu
|
$39,680 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs