Assessment Year | 2005 |
---|---|
Principal Product | Dyed yarn |
NAICS | 313210: Broadwoven Fabric Mills |
SIC | 2211: Broadwoven Fabric Mills, Cotton |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
150,000
ft2
|
Annual Production | 7,500,000
lb
|
Production Hrs. Annual | 8,600
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $358,166 | 21,306,698 |
kWh
|
$0.017 |
Electricity Demand | $283,024 | 33,935 |
kW-mo/yr
|
$8.34 |
Coal | $2,000,000 | 783,167 |
MMBtu
|
$2.55 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $266,878 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Coal Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2121: Increase amount of condensate returned | $27,917 | $25,000 | - | - |
$16,467
-
MMBtu
|
$11,450
-
Tgal
|
- | - | |
02 | 2.1133: Adjust burners for efficient operation | $222,508 | $100,000 | - | - |
$222,508
-
MMBtu
|
- | - | - | |
03 | 2.2136: Install / repair insulation on steam lines | $9,902 | $18,198 | - | - |
$9,902
-
MMBtu
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $423 | $1,006 |
$246
14,612
kWh
|
$177
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.7111: Reduce illumination to minimum necessary levels | $2,395 | $2,000 |
$1,425
84,753
kWh
|
$970
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,733 | $7,500 |
$810
48,180
kWh
|
$550
-
kW-mo/yr
|
- | - | $2,099 | $274 | |
TOTAL RECOMMENDED | $266,878 | $153,704 |
$2,481
147,545
kWh
|
$1,697
-
kW-mo/yr
|
$248,877
-
MMBtu
|
$11,450
-
Tgal
|
$2,099 | $274 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Coal Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs