Assessment Year | 2004 |
---|---|
Principal Product | Adhesive tapes |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $50 M to 100M |
# of Employees | 260 |
Plant Area |
120,000
ft2
|
Annual Production | 3,768,980
thousand feet
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Virginia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $623,860 | 30,233,088 |
kWh
|
$0.021 |
Electricity Demand | $462,430 | 56,052 |
kW-mo/yr
|
$8.25 |
Natural Gas | $714,644 | 120,022 |
MMBtu
|
$5.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $213,016 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,617 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2622: Replace existing chiller with high efficiency model | $96,975 | $360,700 |
$76,222
1,905,540
kWh
|
$22,458
-
kW-mo/yr
|
- |
$(-1,705.0)
-
Tgal
|
|
02 | 2.4322: Use or replace with energy efficient substitutes | $86,931 | $100,000 | n/a |
$(-18,480.0)
(-462,000)
kWh
|
$(-5,445.0)
-
kW-mo/yr
|
$110,856
-
MMBtu
|
- |
03 | 2.1133: Adjust burners for efficient operation | $7,527 | $1,600 | - | - |
$7,527
-
MMBtu
|
- | |
04 | 2.1133: Adjust burners for efficient operation | $10,305 | $5,000 | - | - |
$10,305
-
MMBtu
|
- | |
05 | 2.1212: Operate boilers on high fire setting | $6,289 | $2,100 | - | - |
$6,289
-
MMBtu
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $204 | $79 |
$187
4,680
kWh
|
$17
-
kW-mo/yr
|
- | - | |
07 | 2.7124: Make a practice of turning off lights when not needed | $4,785 | $100 |
$3,696
92,400
kWh
|
$1,089
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $213,016 | $469,579 |
$61,625
1,540,620
kWh
|
$18,119
-
kW-mo/yr
|
$134,977
-
MMBtu
|
$(-1,705.0)
-
Tgal
|
||
TOTAL IMPLEMENTED | $22,617 | $6,700 |
$3,696
92,400
kWh
|
$1,089
-
kW-mo/yr
|
$17,832
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs