| Assessment Year | 2004 |
|---|---|
| Principal Product | Printed catalog inserts |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2752: Commercial Printing, Lithographic |
| Sales Range | $10 M to 50M |
| # of Employees | 42 |
| Plant Area |
31,071
ft2
|
| Annual Production | 700,000,000
pieces
|
| Production Hrs. Annual | 6,720
hrs
|
| Location (State) | Virginia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $66,324 | 3,997,200 |
kWh
|
$0.017 |
| Electricity Demand | $81,271 | 8,729 |
kW-mo/yr
|
$9.31 |
| Electricity Fees | $16,679 | - |
|
- |
| Natural Gas | $143,640 | 17,097 |
MMBtu
|
$8.40 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $25,435 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2414: Use waste heat from hot flue gases to preheat | $9,068 | $23,100 | n/a |
$(-393.0)
(-25,066)
kWh
|
$(-417.0)
-
kW-mo/yr
|
$9,878
-
MMBtu
|
- |
| 02 | 2.7313: Recycle air for heating, ventilation and air conditioning | $4,884 | $6,553 | n/a |
$357
22,783
kWh
|
- |
$4,527
-
MMBtu
|
- |
| 03 | 4.514: Re-arrange equipment layout to reduce handling costs | $3,750 | $5,400 | n/a | - | - | - | $3,750 |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,131 | $2,418 | n/a |
$1,034
65,961
kWh
|
$1,097
-
kW-mo/yr
|
- | - |
| 05 | 2.7241: Install outside air damper / economizer on hvac unit | $2,869 | $10,000 | n/a |
$2,869
183,062
kWh
|
- | - | - |
| 06 | 2.6218: Turn off equipment when not in use | $1,981 | $730 | n/a |
$1,981
126,043
kWh
|
- | - | - |
| 07 | 2.6218: Turn off equipment when not in use | $752 | $1,000 | n/a |
$752
48,000
kWh
|
- | - | - |
| TOTAL RECOMMENDED | $25,435 | $49,201 |
$6,600
420,783
kWh
|
$680
-
kW-mo/yr
|
$14,405
-
MMBtu
|
$3,750 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs