Assessment Year 2002
Principal Product Cigarette filters
NAICS
n/a
SIC 2110:
Sales Range $10
M
to 50
M
# of Employees 150
Plant Area 81,600
ft2
Annual Production 7,500,000,000
pieces
Production Hrs. Annual 6,000
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $144,476 5,272,936
kWh
Electricity Demand $101,283 10,802
kW-mo/yr
Electricity Fees $8,345 -
Natural Gas $19,932 2,863
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $22,529 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $6,370

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Solid Waste (non-haz) Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings
01 2.2437: Recover waste heat from equipment $4,196 $11,000 - - $4,196
-
MMBtu
- - - -
02 2.2437: Recover waste heat from equipment $11,658 $10,000 $11,658
492,087
kWh
- - - - - -
03 2.1331: Burn a less expensive grade of fuel $3,154 $7,500 $6,165
225,000
kWh
$4,239
-
kW-mo/yr
$(-6,750.0)
-
MMBtu
- - $(-500.0) -
04 2.4231: Reduce the pressure of compressed air to the minimum required $1,851 $100 $1,097
40,052
kWh
$754
-
kW-mo/yr
- - - - -
05 3.5315: Lease / purchase baler; sell cardboard to recycler $438 $500 - - - $438
-
lb
- - -
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $909 $887 $538
19,653
kWh
$371
-
kW-mo/yr
- - - - -
07 2.7124: Make a practice of turning off lights when not needed $323 $760 $202
7,360
kWh
$52
-
kW-mo/yr
- - $48 - $21
TOTAL RECOMMENDED $22,529 $30,747 $19,660
784,152
kWh
$5,416
-
kW-mo/yr
$(-2,554.0)
-
MMBtu
$438
-
lb
$48 $(-500.0) $21
TOTAL IMPLEMENTED $6,370 $11,860 $1,299
47,412
kWh
$806
-
kW-mo/yr
$4,196
-
MMBtu
- $48 - $21
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Solid Waste (non-haz) Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings