Assessment Year | 2001 |
---|---|
Principal Product | Socks |
NAICS |
n/a
|
SIC | 2252: Hosiery, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
155,000
ft2
|
Annual Production | 20,000,000
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $428,792 | 7,417,930 |
kWh
|
$0.058 |
Electricity Demand | $149,063 | 18,017 |
kW-mo/yr
|
$8.27 |
Electricity Fees | $11,555 | - |
|
- |
Natural Gas | $230,662 | 38,664 |
MMBtu
|
$5.97 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $108,896 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,005 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $3,205 | $3,300 |
$3,484
52,000
kWh
|
$1,045
-
kW-mo/yr
|
$(-1,324.0)
-
MMBtu
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,659 | $6,560 |
$6,125
91,411
kWh
|
$534
-
kW-mo/yr
|
- | - | |
03 | 2.2437: Recover waste heat from equipment | $6,328 | $5,000 |
$(-469.0)
(-7,000)
kWh
|
$(-98.0)
-
kW-mo/yr
|
$6,895
-
MMBtu
|
- | |
04 | 2.2511: Insulate bare equipment | $2,283 | $1,180 | - | - |
$2,283
-
MMBtu
|
- | |
05 | 2.7313: Recycle air for heating, ventilation and air conditioning | $22,804 | $35,000 |
$2,082
31,080
kWh
|
- |
$20,722
-
MMBtu
|
- | |
06 | 2.1133: Adjust burners for efficient operation | $11,002 | $2,200 | - | - |
$11,002
-
MMBtu
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $3,344 | $2,483 |
$3,075
45,890
kWh
|
$269
-
kW-mo/yr
|
- | - | |
08 | 2.2444: Use hot process fluids to preheat incoming process fluids | $25,814 | $29,000 | - | - |
$25,814
-
MMBtu
|
- | |
09 | 2.3416: Use combined cycle gas turbine generator sets with waste heat boilers connected to turbine exhaust | $27,457 | $100,000 |
$14,800
400,000
kWh
|
$24,900
-
kW-mo/yr
|
$(-8,243.0)
-
MMBtu
|
$(-4,000.0) | |
TOTAL RECOMMENDED | $108,896 | $184,723 |
$29,097
613,381
kWh
|
$26,650
-
kW-mo/yr
|
$57,149
-
MMBtu
|
$(-4,000.0) | ||
TOTAL IMPLEMENTED | $21,005 | $11,243 |
$9,200
137,301
kWh
|
$803
-
kW-mo/yr
|
$11,002
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs