Assessment Year 2000
Principal Product Denim fabric
NAICS
n/a
SIC 2321: Men's and Boys' Shirts, Except Work Shirts
Sales Range $50
M
to 100
M
# of Employees 220
Plant Area 300,000
ft2
Annual Production 45,000
thousand feet
Production Hrs. Annual 8,760
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $529,790 22,447,832
kWh
Electricity Demand $650,320 40,306
kW-mo/yr
Electricity Fees $62,145 -
Natural Gas $607,782 128,616
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $183,646 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $172,702

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings
01 2.2414: Use waste heat from hot flue gases to preheat $150,957 $214,000 $(-1,147.0)
(-48,652)
kWh
$(-1,119.0)
-
kW-mo/yr
$158,516
-
MMBtu
$(-5,293.0)
-
Tgal
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $7,306 $300 $3,785
160,317
kWh
$3,521
-
kW-mo/yr
- -
03 2.7122: Disconnect ballasts $7,600 $6,350 $3,938
167,057
kWh
$3,662
-
kW-mo/yr
- -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $2,637 $7,260 $734
31,067
kWh
$1,903
-
kW-mo/yr
- -
05 2.7124: Make a practice of turning off lights when not needed $6,839 $3,180 $3,648
154,748
kWh
$3,191
-
kW-mo/yr
- -
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $3,675 $50 $1,904
80,598
kWh
$1,771
-
kW-mo/yr
- -
07 2.2426: Use waste heat from flue gases to heat space conditioning air $4,632 $7,499 $(-59.0)
(-2,345)
kWh
- $4,691
-
MMBtu
-
TOTAL RECOMMENDED $183,646 $238,639 $12,803
542,790
kWh
$12,929
-
kW-mo/yr
$163,207
-
MMBtu
$(-5,293.0)
-
Tgal
TOTAL IMPLEMENTED $172,702 $223,830 $10,224
433,470
kWh
$9,255
-
kW-mo/yr
$158,516
-
MMBtu
$(-5,293.0)
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs