Assessment Year 1997
Principal Product Dyed fabric for shirts
NAICS
n/a
SIC 2619:
Sales Range $10
M
to 50
M
# of Employees 240
Plant Area 150,000
ft2
Annual Production 7,500,000
lb
Production Hrs. Annual 7,200
hrs
Location (State) North Carolina

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $259,786 8,654,162
kWh
Electricity Demand $133,083 15,879
kW-mo/yr
Electricity Fees $11,746 -
Natural Gas $914,606 218,206
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $221,254 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings Solid Waste (non-haz) Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings
01 2.4133: Use most efficient type of electric motors $513 $448 $113
11,137
kWh
$400
-
kW-mo/yr
- - - - - -
02 2.7122: Disconnect ballasts $474 $750 $324
10,844
kWh
$150
-
kW-mo/yr
- - - - - -
03 2.2437: Recover waste heat from equipment $1,610 $2,650 - - $1,610
-
MMBtu
- - - - -
04 2.1233: Analyze flue gas for proper air/fuel ratio $3,182 $1,400 - - $3,182
-
MMBtu
- - - - -
05 2.1233: Analyze flue gas for proper air/fuel ratio $759 $700 - - $759
-
MMBtu
- - - - -
06 2.2135: Repair and eliminate steam leaks $72,505 $200 - - $73,505
-
MMBtu
- - $1,000 - $(-2,000.0)
07 3.5315: Lease / purchase baler; sell cardboard to recycler $9,082 $5,200 - - - - $9,282
-
lb
- $800 $(-1,000.0)
08 3.4153: Use counter current rinsing to reduce waste water $22,291 $28,000 - - - $22,291
-
Tgal
- - - -
09 3.4115: Recover and reuse cooling water $109,838 $30,250 - - $61,169
-
MMBtu
$48,669
-
Tgal
- - - -
10 2.1241: Reduce excessive boiler blowdown $1,000 - - - - - - - - $1,000
TOTAL RECOMMENDED $221,254 $69,598 $437
21,981
kWh
$550
-
kW-mo/yr
$140,225
-
MMBtu
$70,960
-
Tgal
$9,282
-
lb
$1,000 $800 $(-2,000.0)
TOTAL IMPLEMENTED - - - - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings Solid Waste (non-haz) Savings Personnel Changes Savings Administrative Changes Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs