Assessment Year | 1996 |
---|---|
Principal Product | Socks |
NAICS |
n/a
|
SIC | 2252: Hosiery, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 350 |
Plant Area |
180,000
ft2
|
Annual Production | 188,160,000
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $170,412 | 4,058,617 |
kWh
|
$0.042 |
Electricity Demand | $39,367 | 14,689 |
kW-mo/yr
|
$2.68 |
Electricity Fees | $24,304 | - |
|
- |
Fuel Oil #6 | $178,843 | 58,125 |
MMBtu
|
$3.08 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $51,914 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,779 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #6 Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,017 | $2,816 |
$840
19,930
kWh
|
$177
-
kW-mo/yr
|
- | - | - | |
02 | 2.7134: Use photocell controls | $1,117 | $630 |
$1,117
26,671
kWh
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $195 | $840 |
$124
2,931
kWh
|
$11
-
kW-mo/yr
|
- | - | $60 | |
04 | 2.2136: Install / repair insulation on steam lines | $1,717 | $2,017 |
$376
10,258
kWh
|
$73
-
kW-mo/yr
|
$1,268
-
MMBtu
|
- | - | |
05 | 2.2443: Re-use or recycle hot or cold process exhaust air | $9,962 | $30,000 | - | - |
$9,962
-
MMBtu
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,451 | $25,000 |
$8,451
201,934
kWh
|
- | - | - | - | |
07 | 2.4239: Eliminate or reduce compressed air usage | $2,733 | $2,720 |
$2,733
65,064
kWh
|
- | - | - | - | |
08 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $24,714 | $54,000 |
$28,829
686,694
kWh
|
$5,519
-
kW-mo/yr
|
$(-9,634.0)
-
MMBtu
|
- | - | |
09 | 3.5313: Increase amount of waste recovered for resale | $2,008 | $200 | - | - | - |
$2,008
-
lb
|
- | |
TOTAL RECOMMENDED | $51,914 | $118,223 |
$42,470
1,013,482
kWh
|
$5,780
-
kW-mo/yr
|
$1,596
-
MMBtu
|
$2,008
-
lb
|
$60 | ||
TOTAL IMPLEMENTED | $6,779 | $9,023 |
$5,190
124,854
kWh
|
$261
-
kW-mo/yr
|
$1,268
-
MMBtu
|
- | $60 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #6 Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs