Assessment Year | 1996 |
---|---|
Principal Product | Fabric for Sheets |
NAICS |
n/a
|
SIC | 2210: |
Sales Range | $10 M to 50M |
# of Employees | 225 |
Plant Area |
275,000
ft2
|
Annual Production | 3,750
thousand feet
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $867,935 | 29,069,168 |
kWh
|
$0.030 |
Electricity Demand | $528,249 | 60,410 |
kW-mo/yr
|
$8.74 |
Electricity Fees | $(-195,415.0) | - |
|
- |
Natural Gas | $74,038 | 24,856 |
MMBtu
|
$2.98 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $76,277 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,675 | $5,094 |
$7,579
236,811
kWh
|
$4,096
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $28,554 | $71,700 |
$8,719
272,567
kWh
|
$4,762
-
kW-mo/yr
|
- |
$1,450
-
lb
|
$13,623 | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $693 | $3,080 |
$347
10,844
kWh
|
$126
-
kW-mo/yr
|
- | - | - | $220 | |
04 | 2.4133: Use most efficient type of electric motors | $8,730 | $7,176 |
$5,645
176,436
kWh
|
$3,085
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $11,689 | $866 |
$7,559
236,225
kWh
|
$4,130
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.7313: Recycle air for heating, ventilation and air conditioning | $12,027 | $5,000 | - | - |
$12,027
-
MMBtu
|
- | - | - | |
07 | 2.2625: Chill water to the highest temperature possible | $2,909 | $50 |
$1,735
54,220
kWh
|
$1,174
-
kW-mo/yr
|
- | - | - | - | |
TOTAL RECOMMENDED | $76,277 | $92,966 |
$31,584
987,103
kWh
|
$17,373
-
kW-mo/yr
|
$12,027
-
MMBtu
|
$1,450
-
lb
|
$13,623 | $220 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs