Assessment Year | 1996 |
---|---|
Principal Product | Coatings |
NAICS |
n/a
|
SIC | 2851: Paints, Varnishes, Lacquers, Enamels, and Allied Products |
Sales Range | $50 M to 100M |
# of Employees | 115 |
Plant Area |
60,000
ft2
|
Annual Production | 2,600
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $188,975 | 4,755,276 |
kWh
|
$0.040 |
Electricity Demand | $73,897 | 10,235 |
kW-mo/yr
|
$7.22 |
Electricity Fees | $19,567 | - |
|
- |
Natural Gas | $56,569 | 11,792 |
MMBtu
|
$4.80 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,681 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,085 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2625: Chill water to the highest temperature possible | $144 | - |
$144
3,517
kWh
|
- | - | - | - | - | |
02 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $14,587 | $25,400 | - | - |
$14,587
-
MMBtu
|
- | - | - | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $738 | $600 | - | - |
$738
-
MMBtu
|
- | - | - | |
04 | 2.8118: Check for accuracy of utility / power meters | $594 | - | - | - | - |
$594
-
Tgal
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $910 | $520 |
$289
7,327
kWh
|
$72
-
kW-mo/yr
|
- | - | - | $549 | |
06 | 2.7134: Use photocell controls | $1,271 | - |
$637
16,120
kWh
|
$634
-
kW-mo/yr
|
- | - | - | - | |
07 | 3.1162: Use less wasteful packaging | $437 | - | - | - | - | - |
$437
-
lb
|
- | |
TOTAL RECOMMENDED | $18,681 | $26,520 |
$1,070
26,964
kWh
|
$706
-
kW-mo/yr
|
$15,325
-
MMBtu
|
$594
-
Tgal
|
$437
-
lb
|
$549 | ||
TOTAL IMPLEMENTED | $2,085 | $1,120 |
$289
7,327
kWh
|
$72
-
kW-mo/yr
|
$738
-
MMBtu
|
- |
$437
-
lb
|
$549 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs