| Assessment Year | 2026 |
|---|---|
| Principal Product | electric repair and distribution shop |
| NAICS | 811219: Other Electronic and Precision Equipment Repair and Maintenance |
| SIC | 7629: Electrical and Electronic Repair Shops, Not Elsewhere Classified |
| Sales Range | less than $500 k |
| # of Employees | 22 |
| Plant Area |
20,500
ft2
|
| Annual Production | 1
pieces
|
| Production Hrs. Annual | 2,600
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $22,903 | 408,200 |
kWh
|
$0.056 | |
| Waste Disposal Costs | |||||
| Water Usage | $2,248 | 305,932 |
Tgal
|
$0.007 | |
| TOTAL YEARLY COSTS | $25,151 | ||||
| RECOMMENDED SAVINGS* | $8,125 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7221: Lower temperature during the winter season and vice-versa | $3,255 | $360 |
$3,255
58,133
kWh
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,819 | $5,038 |
$940
16,783
kWh
|
$879 | |
| 03 | 2.7135: Install occupancy sensors | $1,436 | $2,250 |
$1,436
25,642
kWh
|
- | |
| 04 | 2.7234: Use heat pump for space conditioning | $1,615 | $14,591 |
$1,615
28,800
kWh
|
- | |
| TOTAL RECOMMENDED | $8,125 | $22,239 |
$7,246
129,358
kWh
|
$879 | ||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs