| Assessment Year | 2026 |
|---|---|
| Principal Product | paraffin wax and additives for PVC pipes |
| NAICS | 325211: Plastics Material and Resin Manufacturing |
| SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
| Sales Range | $50 M to 100M |
| # of Employees | 16 |
| Plant Area |
52,000
ft2
|
| Annual Production | 45,000,000
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $358,592 | 4,741,112 |
kWh
|
$0.076 | |
| Electricity Demand | $128,817 | 8,006 |
kW-mo/yr
|
$16.09 | |
| Natural Gas | $87,284 | 37,049 |
MMBtu
|
$2.36 | |
| Waste Disposal Costs | |||||
| Water Usage | $31,393 | 6,291 |
Tgal
|
$4.99 | |
| Water Disposal | $23,460 | 6,291 |
Tgal
|
$3.73 | |
| TOTAL YEARLY COSTS | $629,546 | ||||
| RECOMMENDED SAVINGS* | $86,277 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,194 | - |
$837
11,078
kWh
|
$357
-
kW-mo/yr
|
- | |
| 02 | 2.6127: Maintain air filters by cleaning or replacement | $722 | $600 |
$722
9,556
kWh
|
- | - | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,164 | $2,299 |
$1,164
15,408
kWh
|
- | - | |
| 04 | 2.7135: Install occupancy sensors | $1,099 | $2,700 |
$1,099
14,543
kWh
|
- | - | |
| 05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $6,340 | $1,000 | - | - |
$6,340
-
MMBtu
|
|
| 06 | 2.9114: Use solar heat to make electricty | $70,342 | $285,001 |
$63,902
845,266
kWh
|
$6,440
-
kW-mo/yr
|
- | |
| 07 | 2.2414: Use waste heat from hot flue gases to preheat | $5,416 | $60,000 | - | - |
$5,416
-
MMBtu
|
|
| TOTAL RECOMMENDED | $86,277 | $351,600 |
$67,724
895,851
kWh
|
$6,797
-
kW-mo/yr
|
$11,756
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs