| Assessment Year | 2026 |
|---|---|
| Principal Product | medicinal vials |
| NAICS | 325412: Pharmaceutical Preparation Manufacturing |
| SIC | 2834: Pharmaceutical Preparations |
| Sales Range | $50 M to 100M |
| # of Employees | 175 |
| Plant Area |
151,000
ft2
|
| Annual Production | 10,000,000
pieces
|
| Production Hrs. Annual | 4,125
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $288,979 | 3,467,520 |
kWh
|
$0.083 | |
| Electricity Demand | $27,602 | 6,821 |
kW-mo/yr
|
$4.05 | |
| Natural Gas | $15,059 | 1,480 |
MMBtu
|
$10.18 | |
| Waste Disposal Costs | |||||
| Water Usage | $5,810 | 2,639 |
Tgal
|
$2.20 | |
| Water Disposal | $22,165 | 2,639 |
Tgal
|
$8.40 | |
| TOTAL YEARLY COSTS | $359,615 | ||||
| RECOMMENDED SAVINGS* | $110,561 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $941 | $600 |
$824
9,932
kWh
|
$117
-
kW-mo/yr
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,988 | $9,887 |
$919
11,088
kWh
|
$131
-
kW-mo/yr
|
- | $1,938 | |
| 03 | 2.7135: Install occupancy sensors | $893 | $1,600 |
$893
10,761
kWh
|
- | - | - | |
| 04 | 2.7221: Lower temperature during the winter season and vice-versa | $15,228 | - |
$6,911
83,261
kWh
|
- |
$8,317
-
MMBtu
|
- | |
| 05 | 2.2622: Replace existing chiller with high efficiency model | $88,780 | $279,688 |
$83,219
1,002,638
kWh
|
$5,561
-
kW-mo/yr
|
- | - | |
| 06 | 2.9112: Use solar heat to heat water | $1,731 | $33,250 | - | - |
$1,731
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $110,561 | $325,025 |
$92,766
1,117,680
kWh
|
$5,809
-
kW-mo/yr
|
$10,048
-
MMBtu
|
$1,938 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs