Assessment Year 2025
Principal Product automotive sealant tapes
NAICS 325520: Adhesive Manufacturing
SIC 2891: Adhesives and Sealants
Sales Range $50
M
to 100
M
# of Employees 295
Plant Area 268,000
ft2
Annual Production 3,836
ton
Production Hrs. Annual 6,240
hrs
Location (State) Missouri

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $935,005 13,346,245
kWh
Electricity Demand $493,023 38,373
kW-mo/yr
Natural Gas $25,115 3,776
MMBtu
Waste Disposal Costs
Water Usage $59,067 4,341
Tgal
Water Disposal $17,743 4,341
Tgal
TOTAL YEARLY COSTS $1,529,953
RECOMMENDED SAVINGS* $127,043 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $5,040 $3,750 $5,040
72,000
kWh
- -
02 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,842 - $1,472
21,024
kWh
$370
-
kW-mo/yr
-
03 2.2622: Replace existing chiller with high efficiency model $17,351 $65,000 $12,725
181,786
kWh
$4,626
-
kW-mo/yr
-
04 2.7232: Replace existing hvac unit with high efficiency model $38,194 $140,000 $22,284
318,357
kWh
$5,601
-
kW-mo/yr
$10,309
-
MMBtu
05 2.2622: Replace existing chiller with high efficiency model $3,080 $12,700 $3,080
44,012
kWh
- -
06 2.2625: Chill water to the highest temperature possible $11,303 $10,592 $8,605
122,940
kWh
$2,698
-
kW-mo/yr
-
07 2.2625: Chill water to the highest temperature possible $35,692 $43,968 $27,424
391,779
kWh
$8,268
-
kW-mo/yr
-
08 2.2437: Recover waste heat from equipment $12,321 $23,000 - - $12,321
-
MMBtu
09 2.7221: Lower temperature during the winter season and vice-versa $2,220 $1,050 $890
12,720
kWh
- $1,330
-
MMBtu
TOTAL RECOMMENDED $127,043 $300,060 $81,520
1,164,618
kWh
$21,563
-
kW-mo/yr
$23,960
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs