| Assessment Year | 2003 |
|---|---|
| Principal Product | Wallboard |
| NAICS | 327420: Gypsum Product Manufacturing |
| SIC | 3275: Gypsum Products |
| Sales Range | $50 M to 100M |
| # of Employees | 80 |
| Plant Area |
871,200
ft2
|
| Annual Production | 510,000
thousand feet
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $2,489,754 | 37,630,638 |
kWh
|
$0.066 |
| Electricity Demand | $517,644 | 69,408 |
kW-mo/yr
|
$7.46 |
| Natural Gas | $7,189,880 | 1,334,288 |
MMBtu
|
$5.39 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $3,918,973 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $55,813 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.1213: Direct warmest air to combustion intake | $2,080,457 | $50,000 | - | - |
$2,080,457
-
MMBtu
|
- | |
| 02 | 2.3417: Use waste heat with a closed-cycle gas turbine-generator set to cogenerate electricity and heat | $1,420,987 | $5,000,000 |
$1,956,793
37,630,638
kWh
|
$446,400
-
kW-mo/yr
|
$(-807,006.0)
-
MMBtu
|
$(-175,200.0) | |
| 03 | 2.7131: Add area lighting switches | $8,639 | $303 |
$8,639
126,797
kWh
|
- | - | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $47,174 | - |
$47,174
868,544
kWh
|
- | - | - | |
| 05 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $85,121 | $87,198 |
$86,396
1,307,031
kWh
|
- | - | $(-1,275.0) | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $9,372 | - |
$9,372
142,003
kWh
|
- | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $25,483 | $47,300 |
$20,730
398,649
kWh
|
$4,753
-
kW-mo/yr
|
- | - | |
| 08 | 2.7111: Reduce illumination to minimum necessary levels | $81,073 | $860 |
$66,342
1,267,269
kWh
|
$14,731
-
kW-mo/yr
|
- | - | |
| 09 | 2.7141: Lower light fixtures in high ceiling areas | $159,201 | $2,888 |
$129,506
2,490,509
kWh
|
$29,695
-
kW-mo/yr
|
- | - | |
| 10 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $1,466 | $3,496 | - | - | - | $1,466 | |
| TOTAL RECOMMENDED | $3,918,973 | $5,192,045 |
$2,324,952
44,231,440
kWh
|
$495,579
-
kW-mo/yr
|
$1,273,451
-
MMBtu
|
$(-175,009.0) | ||
| TOTAL IMPLEMENTED | $55,813 | $303 |
$55,813
995,341
kWh
|
- | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs