| Assessment Year | 2024 |
|---|---|
| Principal Product | plastic dispensers |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 500 |
| Plant Area |
465,000
ft2
|
| Annual Production | 378,000,000
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $1,998,908 | 30,643,841 |
kWh
|
$0.065 | |
| Electricity Demand | $462,887 | 55,620 |
kW-mo/yr
|
$8.32 | |
| Natural Gas | $51,388 | 11,451 |
MMBtu
|
$4.49 | |
| Waste Disposal Costs | |||||
| Water Usage | $172,392 | 12,557 |
Tgal
|
$13.73 | |
| TOTAL YEARLY COSTS | $2,685,575 | ||||
| RECOMMENDED SAVINGS* | $71,014 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $18,120 | $1,100 |
$14,429
222,044
kWh
|
$3,691
-
kW-mo/yr
|
|
| 02 | 2.4239: Eliminate or reduce compressed air usage | $6,143 | $20,027 |
$6,143
94,500
kWh
|
- | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,000 | $300 |
$1,702
26,179
kWh
|
$298
-
kW-mo/yr
|
|
| 04 | 2.7135: Install occupancy sensors | $984 | $700 |
$984
15,137
kWh
|
- | |
| 05 | 2.7232: Replace existing hvac unit with high efficiency model | $43,767 | $294,662 |
$27,069
416,455
kWh
|
$16,698
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $71,014 | $316,789 |
$50,327
774,315
kWh
|
$20,687
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs