Assessment Year | 2021 |
---|---|
Principal Product | pressure vessels and heat exchangers |
NAICS | 332313: Plate Work Manufacturing |
SIC | 3443: Fabricated Plate Work (Boiler Shops) |
Sales Range | $10 M to 50M |
# of Employees | 348 |
Plant Area |
210,000
ft2
|
Annual Production | 30
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $126,610 | 1,624,321 |
kWh
|
$0.078 | |
Electricity Demand | $47,291 | 11,518 |
kW-mo/yr
|
$4.11 | |
Natural Gas | $126,465 | 22,840 |
MMBtu
|
$5.54 | |
Waste Disposal Costs | |||||
Water Usage | $7,748 | 1,241 |
Tgal
|
$6.24 | |
TOTAL YEARLY COSTS | $308,114 | ||||
RECOMMENDED SAVINGS* | $75,373 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $23,326 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $7,730 | $7,800 |
$7,730
99,173
kWh
|
- | - | - | - | |
02 | 2.4239: Eliminate or reduce compressed air usage | $4,326 | $480 |
$4,326
55,470
kWh
|
- | - | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $398 | $80 |
$398
5,113
kWh
|
- | - | - | - | |
04 | 2.7231: Use radiant heater for spot heating | $24,773 | $86,550 |
$(-58,420.0)
(-748,980)
kWh
|
$(-14,056.0)
-
kW-mo/yr
|
$97,249
-
MMBtu
|
- | - | |
05 | 4.132: Purchase new equipment to reduce material use / cost | $12,219 | $40,130 |
$(-3,570.0)
(-45,775)
kWh
|
$(-3,092.0)
-
kW-mo/yr
|
- | $18,881 | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $5,527 | $1,395 |
$5,527
70,857
kWh
|
- | - | - | - | |
07 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $2,786 | $11,055 | - | - |
$2,786
-
MMBtu
|
- | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,866 | $3,614 |
$5,866
75,207
kWh
|
- | - | - | - | |
09 | 2.4239: Eliminate or reduce compressed air usage | $9,528 | $625 |
$9,528
122,162
kWh
|
- | - | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,220 | $3,485 |
$1,251
16,044
kWh
|
$107
-
kW-mo/yr
|
- | - | $862 | |
TOTAL RECOMMENDED | $75,373 | $155,214 |
$(-27,364.0)
(-350,729)
kWh
|
$(-17,041.0)
-
kW-mo/yr
|
$100,035
-
MMBtu
|
$18,881 | $862 | ||
TOTAL IMPLEMENTED | $23,326 | $26,514 |
$19,571
251,007
kWh
|
$107
-
kW-mo/yr
|
$2,786
-
MMBtu
|
- | $862 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs