| Assessment Year | 2018 |
|---|---|
| Principal Product | plastic sprayers and dispensers |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 500 |
| Plant Area |
465,000
ft2
|
| Annual Production | 407,000,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $2,232,991 | 30,343,636 |
kWh
|
$0.074 | |
| Electricity Demand | $502,349 | 53,129 |
kW-mo/yr
|
$9.46 | |
| Natural Gas | $7,347 | 5,555 |
MMBtu
|
$1.32 | |
| Waste Disposal Costs | |||||
| Water Usage | $132,426 | 12,275,600 |
Tgal
|
$0.011 | |
| TOTAL YEARLY COSTS | $2,875,112 | ||||
| RECOMMENDED SAVINGS* | $248,975 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $241,964 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $71,753 | $36,641 |
$58,001
794,531
kWh
|
$11,613
-
kW-mo/yr
|
$2,139 | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $61,928 | $33,392 |
$52,401
717,824
kWh
|
$9,527
-
kW-mo/yr
|
- | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $466 | - |
$394
5,400
kWh
|
$72
-
kW-mo/yr
|
- | |
| 04 | 2.2625: Chill water to the highest temperature possible | $107,654 | $78,000 |
$87,719
1,201,628
kWh
|
$19,935
-
kW-mo/yr
|
- | |
| 05 | 3.7391: Implement a maintenance program to keep racks and tanks free of rust, cracks, or corrosion | $163 | - |
$163
2,230
kWh
|
- | - | |
| 06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,011 | $14,440 |
$5,954
81,570
kWh
|
$1,057
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $248,975 | $162,473 |
$204,632
2,803,183
kWh
|
$42,204
-
kW-mo/yr
|
$2,139 | ||
| TOTAL IMPLEMENTED | $241,964 | $148,033 |
$198,678
2,721,613
kWh
|
$41,147
-
kW-mo/yr
|
$2,139 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs