| Assessment Year | 2017 |
|---|---|
| Principal Product | Fabricated structural steel trusses for bridges |
| NAICS | 332312: Fabricated Structural Metal Manufacturing |
| SIC | 3441: Fabricated Structural Metal |
| Sales Range | $1 M to 5M |
| # of Employees | 170 |
| Plant Area |
320,000
ft2
|
| Annual Production | 1,000
pieces
|
| Production Hrs. Annual | 4,000
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $336,010 | 2,354,330 |
kWh
|
$0.14 |
| Electricity Demand | $30,509 | 12,873 |
kW-mo/yr
|
$2.37 |
| Natural Gas | $3,869 | 881 |
MMBtu
|
$4.39 |
| TOTAL YEARLY COSTS | $370,388 | |||
| RECOMMENDED SAVINGS* | $34,645 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $34,645 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,680 | - |
$6,680
47,042
kWh
|
- | - | - | |
| 02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $605 | - |
$605
4,207
kWh
|
- | - | - | |
| 03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $70 | - |
$70
492
kWh
|
- | - | - | |
| 04 | 2.2437: Recover waste heat from equipment | $3,933 | $1,539 | - | - |
$3,933
-
MMBtu
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,398 | $22,603 |
$13,562
95,040
kWh
|
$676
-
kW-mo/yr
|
- | $4,160 | |
| 06 | 2.7111: Reduce illumination to minimum necessary levels | $403 | $100 |
$384
2,688
kWh
|
$19
-
kW-mo/yr
|
- | - | |
| 07 | 2.7135: Install occupancy sensors | $1,231 | $950 |
$1,142
8,005
kWh
|
$88
-
kW-mo/yr
|
- | - | |
| 08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,326 | $200 |
$3,236
22,672
kWh
|
$90
-
kW-mo/yr
|
- | - | |
| TOTAL RECOMMENDED | $34,645 | $25,392 |
$25,679
180,146
kWh
|
$874
-
kW-mo/yr
|
$3,933
-
MMBtu
|
$4,160 | ||
| TOTAL IMPLEMENTED | $34,645 | $25,392 |
$25,679
180,146
kWh
|
$874
-
kW-mo/yr
|
$3,933
-
MMBtu
|
$4,160 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs