Assessment Year | 2016 |
---|---|
Principal Product | Dental chairs, fixtures |
NAICS | 339114: Dental Equipment and Supplies Manufacturing |
SIC | 3843: Dental Equipment and Supplies |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
128,000
ft2
|
Annual Production | 15,000
pieces
|
Production Hrs. Annual | 3,200
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $62,434 | 856,960 |
kWh
|
$0.073 |
Electricity Demand | $23,694 | 3,977 |
kW-mo/yr
|
$5.96 |
Natural Gas | $16,705 | 2,172 |
MMBtu
|
$7.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,948 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,909 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $162 | - |
$124
1,696
kWh
|
$38
-
kW-mo/yr
|
|
02 | 2.4239: Eliminate or reduce compressed air usage | $6,016 | $7,700 |
$5,174
70,962
kWh
|
$842
-
kW-mo/yr
|
|
03 | 2.4221: Install compressor air intakes in coolest locations | $859 | $1,000 |
$656
8,999
kWh
|
$203
-
kW-mo/yr
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,550 | $920 |
$1,954
26,796
kWh
|
$596
-
kW-mo/yr
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,509 | $34,515 |
$8,042
110,288
kWh
|
$2,467
-
kW-mo/yr
|
|
06 | 2.6212: Turn off equipment during breaks, reduce operating time | $632 | - |
$632
8,672
kWh
|
- | |
07 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,393 | - |
$1,393
19,110
kWh
|
- | |
08 | 2.7135: Install occupancy sensors | $1,139 | $300 |
$1,139
15,620
kWh
|
- | |
09 | 2.7134: Use photocell controls | $1,863 | $750 |
$1,863
25,550
kWh
|
- | |
10 | 2.4133: Use most efficient type of electric motors | $825 | $3,500 |
$632
8,665
kWh
|
$193
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $25,948 | $48,685 |
$21,609
296,358
kWh
|
$4,339
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $15,909 | $38,935 |
$12,653
173,531
kWh
|
$3,256
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs