ITAC Assessment: MZ0147
ITAC logo
ITAC Assessment: MZ0147
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2014
Principal Product plastic bags
NAICS 326111: Plastics Bag and Pouch Manufacturing
SIC 2673: Plastics, Foil, and Coated Paper Bags
Sales Range $10
M
to 50
M
# of Employees 142
Plant Area 130,000
ft2
Annual Production 189,431,247
pieces
Production Hrs. Annual 8,544
hrs
Location (State) Missouri

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $558,610 11,223,956
kWh
Electricity Demand $41,474 20,136
kW-mo/yr
Natural Gas $10,051 3,690
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $33,103 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $20,537

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7132: Install timers on light switches in little used areas $871 $360 $871
17,419
kWh
-
02 2.7132: Install timers on light switches in little used areas $63 $235 $63
1,269
kWh
-
03 2.7132: Install timers on light switches in little used areas $63 $235 $63
1,269
kWh
-
04 2.7132: Install timers on light switches in little used areas $423 $470 $423
8,459
kWh
-
05 2.7142: Utilize higher efficiency lamps and/or ballasts $10,562 $42,645 $9,850
196,999
kWh
$712
-
kW-mo/yr
06 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available $1,184 $600 $1,184
23,680
kWh
-
07 2.2437: Recover waste heat from equipment $9,950 $5,290 $8,427
168,538
kWh
$1,523
-
kW-mo/yr
08 2.2511: Insulate bare equipment $2,616 $2,613 $2,616
52,315
kWh
-
09 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,212 $420 $3,982
79,631
kWh
$230
-
kW-mo/yr
10 2.6127: Maintain air filters by cleaning or replacement $3,158 $250 $2,985
59,708
kWh
$173
-
kW-mo/yr
TOTAL RECOMMENDED $33,103 $53,118 $30,465
609,287
kWh
$2,638
-
kW-mo/yr
TOTAL IMPLEMENTED $20,537 $45,215 $19,422
388,434
kWh
$1,115
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs