| Assessment Year | 1996 |
|---|---|
| Principal Product | Rubber Bands |
| NAICS |
n/a
|
| SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 210 |
| Plant Area |
110,000
ft2
|
| Annual Production | 22,000,000
lb
|
| Production Hrs. Annual | 6,257
hrs
|
| Location (State) | Arkansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $183,363 | 8,849,355 |
kWh
|
$0.021 |
| Electricity Demand | $303,105 | 18,504 |
kW-mo/yr
|
$16.38 |
| Natural Gas | $30,540 | 6,852 |
MMBtu
|
$4.46 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $63,026 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $29,814 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,485 | $120 |
$951
45,428
kWh
|
$1,534
-
kW-mo/yr
|
- | |
| 02 | 2.4133: Use most efficient type of electric motors | $6,496 | $11,870 |
$2,190
104,338
kWh
|
$4,306
-
kW-mo/yr
|
- | |
| 03 | 2.7111: Reduce illumination to minimum necessary levels | $7,972 | $1,745 |
$3,270
155,627
kWh
|
$4,702
-
kW-mo/yr
|
- | |
| 04 | 2.2612: Use cooling tower water instead of refrigeration | $25,240 | $20,000 |
$12,112
577,081
kWh
|
$13,128
-
kW-mo/yr
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $929 | - |
$318
15,240
kWh
|
$611
-
kW-mo/yr
|
- | |
| 06 | 2.3212: Optimize plant power factor | $5,388 | $1,000 |
$5,388
256,741
kWh
|
- | - | |
| 07 | 2.4239: Eliminate or reduce compressed air usage | $13,027 | $4,900 |
$4,970
236,811
kWh
|
$8,057
-
kW-mo/yr
|
- | |
| 08 | 3.4151: Minimize water usage | $1,489 | $1,000 | - | - |
$1,489
-
Tgal
|
|
| TOTAL RECOMMENDED | $63,026 | $40,635 |
$29,199
1,391,266
kWh
|
$32,338
-
kW-mo/yr
|
$1,489
-
Tgal
|
||
| TOTAL IMPLEMENTED | $29,814 | $18,890 |
$13,817
658,558
kWh
|
$14,508
-
kW-mo/yr
|
$1,489
-
Tgal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs