Assessment Year | 2012 |
---|---|
Principal Product | Electrical Insulators |
NAICS | 335311: Power, Distribution, and Specialty Transformer Manufacturing |
SIC | 3612: Power, Distribution, and Specialty Transformers |
Sales Range | $10 M to 50M |
# of Employees | 85 |
Plant Area |
125,000
ft2
|
Annual Production | 1,500,000
pieces
|
Production Hrs. Annual | 8,160
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $85,892 | 2,445,223 |
kWh
|
$0.035 |
Electricity Demand | $54,023 | 4,815 |
kW-mo/yr
|
$11.22 |
Natural Gas | $50,256 | 6,518 |
MMBtu
|
$7.71 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $48,186 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,009 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $3,057 | $1,160 |
$2,079
59,236
kWh
|
$977
-
kW-mo/yr
|
- | |
02 | 2.4239: Eliminate or reduce compressed air usage | $7,672 | $3,000 |
$6,673
190,125
kWh
|
$998
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,711 | $27,900 |
$10,687
304,482
kWh
|
$5,024
-
kW-mo/yr
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $621 | - |
$422
12,024
kWh
|
$198
-
kW-mo/yr
|
- | |
05 | 2.2622: Replace existing chiller with high efficiency model | $6,785 | $30,700 |
$2,396
68,460
kWh
|
$4,389
-
kW-mo/yr
|
- | |
06 | 2.7231: Use radiant heater for spot heating | $12,505 | $14,400 |
$129
3,722
kWh
|
$722
-
kW-mo/yr
|
$11,654 | |
07 | 2.6127: Maintain air filters by cleaning or replacement | $1,836 | $900 |
$1,249
35,575
kWh
|
$587
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $48,186 | $78,060 |
$23,636
673,625
kWh
|
$12,896
-
kW-mo/yr
|
$11,654 | ||
TOTAL IMPLEMENTED | $28,009 | $60,660 |
$16,833
479,777
kWh
|
$11,176
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs