Assessment Year 2011
Principal Product printing services
NAICS 511110: Newspaper Publishers
SIC 2711: Newspapers: Publishing, or Publishing and Printing
Sales Range $10
M
to 50
M
# of Employees 230
Plant Area 145,000
ft2
Annual Production 1,200
ton
Production Hrs. Annual 7,920
hrs
Location (State) Missouri

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $129,124 3,181,495
kWh
Electricity Demand $141,384 8,220
kW-mo/yr
Natural Gas $20,419 1,712
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $59,295 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $38,065

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,976 $820 $2,790
69,750
kWh
$2,186
-
kW-mo/yr
02 2.7221: Lower temperature during the winter season and vice-versa $515 - $515
12,884
kWh
-
03 2.7423: Reduce heat gain by window tinting $409 $554 $409
10,266
kWh
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $9,134 $18,500 $9,134
228,355
kWh
-
05 2.7135: Install occupancy sensors $81 $170 $81
2,028
kWh
-
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $110 - $110
2,738
kWh
-
07 2.7221: Lower temperature during the winter season and vice-versa $22,840 - $22,840
571,066
kWh
-
08 2.3131: Reschedule plant operations or reduce load to avoid peaks $21,230 $1,000 - $21,230
-
kW-mo/yr
TOTAL RECOMMENDED $59,295 $21,044 $35,879
897,087
kWh
$23,416
-
kW-mo/yr
TOTAL IMPLEMENTED $38,065 $20,044 $35,879
897,087
kWh
$2,186
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs