Assessment Year | 2010 |
---|---|
Principal Product | automobile and truck brake handle and linkage |
NAICS | 336340: Motor Vehicle Brake System Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $50 M to 100M |
# of Employees | 240 |
Plant Area |
90,000
ft2
|
Annual Production | 150,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $92,444 | 2,863,500 |
kWh
|
$0.032 |
Electricity Demand | $8,301 | 5,700 |
kW-mo/yr
|
$1.46 |
Natural Gas | $76,207 | 67,185 |
MMBtu
|
$1.13 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,780 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $48,773 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $823 | $300 |
$823
13,530
kWh
|
- | - | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,416 | - |
$2,416
39,537
kWh
|
- | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $19,012 | - |
$19,012
311,126
kWh
|
- | - | - | |
04 | 2.7492: Use proper thickness of insulation on building envelope | $180 | $170 | - | - |
$180
-
MMBtu
|
- | |
05 | 2.7135: Install occupancy sensors | $5,075 | $6,650 |
$5,075
80,549
kWh
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,075 | $3,960 |
$1,677
26,624
kWh
|
$1,398
-
kW-mo/yr
|
- | - | |
07 | 2.6218: Turn off equipment when not in use | $217 | $150 |
$217
3,440
kWh
|
- | - | - | |
08 | 2.4239: Eliminate or reduce compressed air usage | $2,410 | $2,800 |
$2,410
38,350
kWh
|
- | - | - | |
09 | 2.8112: Combine utility meters | $288 | - | - | - | - | $288 | |
10 | 3.1192: Reduce scrap production | $3,156 | - |
$1,618
25,680
kWh
|
- |
$1,538
-
MMBtu
|
- | |
11 | 2.2211: Use optimum temperature | $1,228 | - |
$1,228
19,502
kWh
|
- | - | - | |
12 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $17,900 | $37,600 |
$17,900
293,443
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $55,780 | $51,630 |
$52,376
851,781
kWh
|
$1,398
-
kW-mo/yr
|
$1,718
-
MMBtu
|
$288 | ||
TOTAL IMPLEMENTED | $48,773 | $47,670 |
$47,055
766,118
kWh
|
- |
$1,718
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs