Assessment Year | 2023 |
---|---|
Principal Product | Administration |
NAICS | 921190: Other General Government Support |
SIC | 8399: Social Services, Not Elsewhere Classified |
Sales Range | less than $500 k |
# of Employees | 80 |
Plant Area |
43,382
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $38,745 | 520,360 |
kWh
|
$0.074 |
Electricity Demand | $24,519 | 1,297 |
kW-mo/yr
|
$18.90 |
Electricity Fees | $5,595 | - |
|
- |
Natural Gas | $27,133 | 2,523 |
MMBtu
|
$10.75 |
TOTAL YEARLY COSTS | $95,992 | |||
RECOMMENDED SAVINGS* | $15,561 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2211: Use optimum temperature | $577 | - |
$106
1,514
kWh
|
- |
$471
-
MMBtu
|
|
02 | 2.7111: Reduce illumination to minimum necessary levels | $771 | - |
$697
9,963
kWh
|
$74
-
kW-mo/yr
|
- | |
03 | 2.7291: Reschedule and rearrange multiple-source heating systems | $5,210 | $600 |
$1,833
26,182
kWh
|
- |
$3,378
-
MMBtu
|
|
04 | 2.7224: Reduce space conditioning during non-working hours | $4,480 | $3,150 |
$1,576
22,514
kWh
|
- |
$2,904
-
MMBtu
|
|
05 | 2.2511: Insulate bare equipment | $23 | $14 | - | - |
$23
-
MMBtu
|
|
06 | 2.7492: Use proper thickness of insulation on building envelope | $38 | $36 | - | - |
$38
-
MMBtu
|
|
07 | 2.7311: Ventilation system to shut off when room is not in use | $2,177 | $4,350 |
$766
10,941
kWh
|
- |
$1,411
-
MMBtu
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $366 | $1,749 |
$267
3,816
kWh
|
$99
-
kW-mo/yr
|
- | |
09 | 2.7135: Install occupancy sensors | $54 | $33 |
$54
770
kWh
|
- | - | |
10 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $332 | $648 |
$332
4,736
kWh
|
- | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,533 | $5,241 |
$1,389
19,843
kWh
|
$144
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $15,561 | $15,821 |
$7,020
100,279
kWh
|
$317
-
kW-mo/yr
|
$8,225
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs