| Assessment Year | 2024 |
|---|---|
| Principal Product | They use reactive injection molding to produce plastic products, most often it is bumpers for various vehicles. |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 96 |
| Plant Area |
135,000
ft2
|
| Annual Production | 1,205,890
lb
|
| Production Hrs. Annual | 4,810
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $154,608 | 3,744,601 |
kWh
|
$0.041 |
| Electricity Demand | $150,942 | 7,563 |
kW-mo/yr
|
$19.96 |
| Electricity Fees | $22,036 | - |
|
- |
| Natural Gas | $134,196 | 27,627 |
MMBtu
|
$4.86 |
| TOTAL YEARLY COSTS | $461,782 | |||
| RECOMMENDED SAVINGS* | $77,576 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $18,952 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $29,504 | $21,472 |
$13,143
328,571
kWh
|
$16,362
-
kW-mo/yr
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $493 | $160 |
$186
4,660
kWh
|
$307
-
kW-mo/yr
|
- | |
| 03 | 2.6211: Conserve energy by efficient use of vending machines | $275 | $720 |
$163
4,080
kWh
|
$111
-
kW-mo/yr
|
- | |
| 04 | 2.7111: Reduce illumination to minimum necessary levels | $330 | - |
$138
3,448
kWh
|
$192
-
kW-mo/yr
|
- | |
| 05 | 2.7124: Make a practice of turning off lights when not needed | $48 | - |
$21
529
kWh
|
$26
-
kW-mo/yr
|
- | |
| 06 | 2.7135: Install occupancy sensors | $506 | $138 |
$225
5,637
kWh
|
$281
-
kW-mo/yr
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,007 | $593 |
$840
20,998
kWh
|
$1,167
-
kW-mo/yr
|
- | |
| 08 | 2.7243: Improve air circulation with destratification fans / other methods | $7,101 | $34,200 | - | - |
$7,101
-
MMBtu
|
|
| 09 | 2.7442: Keep doors and windows shut when not on use | $362 | - |
$75
1,867
kWh
|
$134
-
kW-mo/yr
|
$153
-
MMBtu
|
|
| 10 | 2.7447: Install vinyl strip / high speed / air curtain doors | $15,537 | $3,386 | - | - |
$15,537
-
MMBtu
|
|
| 11 | 2.7492: Use proper thickness of insulation on building envelope | $158 | $617 | - | - |
$158
-
MMBtu
|
|
| 12 | 2.9114: Use solar heat to make electricty | $21,256 | $158,490 |
$7,027
175,665
kWh
|
$14,230
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $77,576 | $219,776 |
$21,818
545,455
kWh
|
$32,808
-
kW-mo/yr
|
$22,949
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $18,952 | $4,277 |
$1,348
33,691
kWh
|
$1,914
-
kW-mo/yr
|
$15,690
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs