| Assessment Year | 2026 |
|---|---|
| Principal Product | Plastic Products |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 50 |
| Plant Area |
55,000
ft2
|
| Annual Production | 13,000,000
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Mississippi |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $210,614 | 2,601,300 |
kWh
|
$0.081 |
| Electricity Demand | $17,316 | 6,687 |
kW-mo/yr
|
$2.59 |
| Electricity Fees | $48,438 | - |
|
- |
| TOTAL YEARLY COSTS | $276,368 | |||
| RECOMMENDED SAVINGS* | $77,105 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $533 | $3,825 |
$533
6,576
kWh
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,048 | $1,973 |
$5,048
62,323
kWh
|
- | |
| 03 | 2.4321: Upgrade obsolete equipment | $7,585 | $97,765 |
$7,585
94,816
kWh
|
- | |
| 04 | 2.7135: Install occupancy sensors | $868 | $1,889 |
$868
10,712
kWh
|
- | |
| 05 | 2.9114: Use solar heat to make electricty | $58,484 | $501,281 |
$54,538
673,865
kWh
|
$3,946
-
kW-mo/yr
|
|
| 06 | 2.7425: Clean or color roof to reduce solar load | $4,587 | $19,764 |
$4,587
56,629
kWh
|
- | |
| TOTAL RECOMMENDED | $77,105 | $626,497 |
$73,159
904,921
kWh
|
$3,946
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs